Thermostatic flow limitation valve
VTF320
- Simple installation and usage
- Responsive, quick and accurate
- Flow limitation with 55°C
- System optimization
- Exploitation cost reduction
- Energy savings
Thermostatic flow limitation valves applicable where flow limitation and temperature safety is required. Series VTF300 are designed for potable hot water circulation systems to secure the right PHW-C temperature. The valves allow to optimize the system, keep it efficient and decries the exploitation cost.
The VTF320 closes the flow of the potable water circulation when the desired temperature is reached. This function allows to optimize the PHW system by shutting off zones which are already heated, and/or continue to heat zones which are below desired temperature. Thermostatic flow limitation valves applicable where flow limitation and temperature safety is required.
VTF322, External thread
Art.no. | Reference | Closing temperature [°C] | Kvs | Connection E | A [mm] | B [mm] | C [mm] | D [mm] | E | Weight [kg] |
31220300 | VTF322 | 55 | 1,8 | G ¾" | 70 | 28 | 52 | 46 | G ¾" | 0,45 |
Technical data
Pressure class: | PN 10 |
Working pressure: | 1,0 MPa |
Connections: | External thread, ISO 228/1 |
Close off pressure: | 600 kPa |
Operational dynamic differential pressure: | max. 300 kPa |
Media temperature, max. continuously: | +95 °C |
Media temperature, max. temporarily: | +100 °C |
Media temperature, min.: | 0 °C |
Closing temperature accuracy: | ±2 °C |
Material, Valve housing and other metal parts with fluid contact: | DZR brass CW625N, resistant to dezincification |
Conformity
Download area
Type | Preview | Download |
Data Sheet | VTF320 | |
Installation instruction | VTF320 | |
Certificate | Declaration of Conformity, VTF320 | |
Certificate | Declaration of Conformity UKCA, VTF320 | |
Certificate | Building Product Declaration BPD3, VTF300 | |
Certificate | ÜA R-15.2.4-22-17605 (AT), VTF320 | |
Certificate | KIWA-21-DW-10120, VTF320 | |
Certificate | Certificate of conformity UA, VTF320 | |
Approval | PZH-certificate (PL), VTF320 | |
Image | VTF322, high res | |
2D Image | VTF320 | |
3D drawing (stp file) | VTF322 |
Applications
Indirect potable hot water temperature control with a PHW controller CRS211 and flow limitation valve VTF320