Thermostatic mixing valve
VTA350, VTA550
- Anti-scald and anti-legionella protection.
- Accuracy of regulation.
- Suitable for HWC (hot water circulation).
The series VTA350/VTA550 for domestic hot water distribution, anti-scalded tempering in line applications and where further temperature control devices have been installed at the water taps. These series of valves are also suitable for domestic hot water installations equipped with HWC (hot water circulation).
Product range
VTA351, Internal thread
Art.no. | Reference | Temp. range [⁰C] | Kvs | Connection E | A [mm] | B [mm] | C [mm] | D [mm] | Weight [kg] |
31104900 | VTA351 | 35 - 60 | 1,6 | Rp ¾" | 70 | 42 | 52 | 46 | 0,48 |
VTA352/VTA552, External thread
Art.no. | Reference | Temp. range [⁰C] | Kvs | Connection E | A [mm] | B [mm] | C [mm] | D [mm] | Weight [kg] |
31660100 | VTA552 | 20 - 43 | 3,2 | G 1" | 84 | 50 | 60 | 56 | 0,78 |
31660400 | VTA552 | 20 - 43 | 3,5 | G 1¼" | 84 | 50 | 60 | 56 | 0,87 |
31105000 | VTA352 | 35 - 60 | 1,5 | G ¾" | 70 | 42 | 52 | 46 | 0,45 |
31105100 | VTA352 | 35 - 60 | 1,6 | G 1" | 70 | 42 | 52 | 46 | 0,48 |
31660200 | VTA552 | 45 - 65 | 3,2 | G 1" | 84 | 50 | 60 | 56 | 0,78 |
31660500 | VTA552 | 45 - 65 | 3,5 | G 1¼" | 84 | 50 | 60 | 56 | 0,87 |
31660300 | VTA552 | 50 - 75 | 3,2 | G 1" | 84 | 50 | 60 | 56 | 0,78 |
31660600 | VTA552 | 50 - 75 | 3,5 | G 1¼" | 84 | 50 | 60 | 56 | 0,87 |
VTA352, External thread and integrated check valves
Art.no. | Reference | Temp. range [⁰C] | Kvs | Connection E | A [mm] | B [mm] | C [mm] | D [mm] | F [mm] | Weight [kg] | Note |
31106100 | VTA352 | 35 - 60 | 1,5 | G 1" | 70 | 42 | 52 | 46 | 74 | 0,48 | Two checkvalves for both hot and cold water are integrated |
VTA353, Compression fittings
Art.no. | Reference | Temp. range [⁰C] | Kvs | Connection E | A [mm] | B [mm] | C [mm] | D [mm] | Weight [kg] |
31105200 | VTA353 | 35 - 60 | 1,5 | CPF 22 mm | 70 | 42 | 52 | 46 | 0,57 |
Installation support
Operation
Installation example
Documents
Technical data
Technical data
Pressure class: | PN 10 |
Working pressure: | 1,0 MPa |
max. Differential pressure, Mixing: | 0,3 MPa |
Temperature stability: | VTA350: ±2 °C*; VTA550: ±4 °C**; * Valid at unchanged hot/cold water pressure, minimum flow rate 4 l/min. Minimum temperature difference between hot water inlet and mixed water outlet 10°C. ** Valid at unchanged hot/cold water pressure, minimum flow rate 9 l/min. Minimum temperature difference between hot water inlet and mixed water outlet 10°C. |
Media temperature, max.: | +95 °C |
Media temperature VTA550 temporarily max.: | +100 °C |
Connections, Internal thread (Rp): | EN 10226-1 |
Connections, External thread (G): | ISO 228/1 |
Connections, External thread (R): | EN 10226-1 |
Connections, Compression fitting (CPF): | EN 1254-2 |
Material, Valve housing and other metal parts with fluid contact: | Dezincification resistant brass, DZR |
Conformity
Dimensioning
Accessories and spare parts
Spare parts
Connection kit KTD200, KTD300
Connection kit KCD300
Download area
Download area
Type | Preview | Download |
Data Sheet | VTA350, VTA550 | |
Installation instruction | VTA350 | |
Installation Instruction | VTA550 | |
Certificate | Declaration of Conformity, VTA350/VTA550 | |
Certificate | Declaration of Conformity UKCA, VTA350/VTA550 | |
Certificate | Building Product Declaration BPD3, VTA350 | |
Certificate | Building Product Declaration BPD3, VTA550 | |
Certificate | ÜA R-15.2.4-22-17605 (AT), VTA350/VTA550 | |
Certificate | KIWA-21-DW-10120, VTA350 | |
Certificate | KIWA-21-DW-10122, VTA550 | |
Certificate | EAC certificate (RU), VTA350/VTA550 | |
Certificate | Certificate of conformity UA, VTA350/VTA550 | |
Approval | PZH-certificate (PL), VTA350/VTA550 | |
Image | VTA351, high res | |
Image | VTA352, high res | |
Image | VTA352 with Check Valves, high res | |
Image | VTA353, high res | |
Image | VTA552, high res | |
Image | VTA552 with adapters, high res | |
2D Image | VTA352 with check valves | |
2D Image | VTA550 | |
2D Image | VTA552 with adapters | |
3D drawing (stp file) | VTA352 G ¾" | |
3D drawing (stp file) | VTA352 CV G 1" | |
3D drawing (stp file) | VTA552 G 1" | |
3D drawing (stp file) | VTA552 R ¾" |
Applications
Applications
Indirect potable hot water temperature control with a PHW controller CRS211.
Domestic hot water system with symmetrical flow.
Indirect potable hot water temperature control with a PHW controller CRS211 and flow limitation valve VTF320