Controller
CRB200
- Room temperature Controller
- Wired or wireless communication between room unit and main controller
- ESBE Smart Software and Self-Adaptive System
- Low noise level
- Accurate and precise control
- Constant temperature working mode available
- Possible upgrade to outdoor temperature compensated controller
- Possible upgrade to combined outdoor and room temperature controller
- Possible upgrade to pump control (ON/OFF)
The Series CRB200 is a room temperature Controller with integrated actuator dedicated for ESBE Rotary valves Series VRG.
The Controllers Series CRB200 are equipped with ESBE Smart Software and Self-Adaptive System which not only increase the performance of the device but allows to upgrade the controller to weather compensated or combined temperature control working principle. The Controller can also be used as a constant temperature Controller.
The Series CRB200 is available in two versions: CRB210 with wired communication and CRB220 with wireless communication between the room unit and the main Controller.
CRB200
Art.no. | Reference | Voltage [V AC] | Torque [Nm] | Room display unit | Weight [kg] | Replaces |
12663100 | CRB211 | 230 | 6 | Cable | 0,7 | 12660100 |
12665200 | CRB221 | 230 | 6 | Wireless | 0,9 | 12662200 |
Install ESBE Controller - CRB200
Change opening direction – ESBE Controllers (CRx200)
Change target temperature – ESBE Controllers (CRx200)
Change maximum/minimum flow temperature – ESBE Controllers (CRx200)
External activation of T2 – ESBE Controllers (CRx200)
Install radio module for wireless communication – ESBE Controller CRB211
Configure ESBE Controller CRB200
Upgrade your ESBE Controller – CRA200 to CRB200
Upgrade your ESBE Controller – CRB200 to CRC200
Upgrade your ESBE Controller – CRB200 to CRD200
Upgrade your ESBE Controller – CRC200 to CRB200
Installation example
Documents
Technical data
Sensors: | Temperature sensor type NTC |
Enclosure rating: | Actuator unit: IP41; Room unit: IP20 |
Protection class: | II |
Power supply: | Actuator unit: 230 ± 10% V AC, 50 Hz; Room unit - wireless: 2x1,5V LR6/AA |
Power consumption: | 10 VA |
Battery endurance, wireless room display unit: | 1 year |
Torque: | 6 Nm |
ERP temperature controls class: | IV |
Energy efficiency contribution: | 2 % |
Radio frequency: | Wireless room unit - 868 MHz; ITU region 1 approved acc. to EN 300220-2 |
Running time at max. speed: | 30 s |
Weight: | 1,3 kg |
Supplied parts: | • Actuator with integrated controller |
• Flow temperature sensor | |
• EU adapter 230V | |
• Room unit | |
• Communication cable between room unit and actuator (CRB210) | |
Ambient temperature, max.: | +50 °C |
Ambient temperature, min.: | +5 °C |
Temperature range, Flow temperature sensor: | +5 to +95 °C |
Temperature range, Room unit (Indoor sensor): | +5 to +30 °C |
Conformity
Wiring
Adaptor Kits
Spare parts
Download area
Type | Preview | Download |
Data sheet | CRB200 | |
Installation instruction | CRB200 - Assembly | |
Installation instruction | CRB200 | |
Certificate | Declaration of Conformity, CRB200 | |
Certificate | Declaration of Conformity UKCA, CRB200 | |
Certificate | Building Product Declaration BPD3, CRB200 | |
Certificate | EAC certificate, CRB200 | |
Certificate | Certificate of conformity UA, CRB200 | |
Image | CRB211, high res | |
Image | CRB221, high res | |
Image | CRB912/CRB913 Room unit, high res | |
2D Image | CRB210, CRB220 | |
2D Image | CRB912/CRB913 Room unit | |
3D drawing (stp file) | CRB210, CRB220 | |
3D drawing (stp file) | CRB912/CRB913 Room unit |
Applications
Indoor / Outdoor based regulated under floor heating with multiple zones.
Radiator circuit with multiple under floor heating zones.
Valve-controlled radiator circuit with raised return temperature.
Heat system with radiator circuit and under floor system.
Bivalent heat system with independent radiator circuit and under floor system.
Bivalent heat system with independent radiator circuit and under floor system.
Heat system with independent radiator circuit and under floor system.
Radiator circuit together with one under floor heating zone.
Complete solid fuel application with domestic hot water and solar system.
4-way bivalent together with controller for radiator circuit.
Domestic hot water control and regulation of under floor heating for systems with district heating.
Heat system with independent radiator circuit and under floor system.
Heat system with radiator circuit and under floor system.